Products

HONEYWELL 129464N UV Flame Sensing Tube (129464)

REQUEST A QUOTE

  • Component Type: Replacement UV Power Sensing Tube with Base
  • Operating Temperature: -40°F to +250°F (-40°C to +121°C)
  • Dimensions: Height: 69 mm
  • Diameter: 19 mm
  • Weight: 0.038 kg (0.08 lbs)
  • Tariff Code: 85408900
  • Flame Amplifiers: Compatible with Honeywell R7849A/B UV flame amplifiers used in standard 7800 SERIES Burner Management Systems.
  • Fuel Profiles: Engineered to monitor ultraviolet radiation from gas-, oil-, and coal-fired burners.
  • High-Temperature Environments: If installing the companion primary detector in areas exceeding the baseline temperature limit, utilize specialized Honeywell F leadwires (Specification No. 32004766-003). This specialized wiring is continuously rated up to 400°F (250°C).
  • Wiring Considerations: For non-high-temperature sections, utilize moisture-resistant No. 14 AWG wire rated for the peak ambient temperatures expected inside the burner enclosure.

Brand New HONEYWELL 129464N Photocell. In stock — ships worldwide within 5-10 days.

1-year warranty against manufacturing defects. Contact us for pricing — reply within 24 hours.

  • Availability shown is for reference only and will be confirmed at the time the order is processed.
  • Published quantities may change without prior notice.
  • The customer is responsible for verifying part number and specifications before confirming the purchase.
  • Certain products may be considered special order items depending on availability.
  • Extensive experience in industrial automation.
  • We source hard-to-find or discontinued parts.
  • Network of international manufacturers and distributors.
  • Personalized support for urgent requirements.